Electrical Troubleshooting Quiz, July 10, 2012

July 10, 2012
After the first motor replacement, problems, such as inexplicable motor overload blowouts, started occurring.

The two large compressors for plant air are housed in a small cinder block structure tacked onto the main building. The motors have each been replaced twice in the past five years. After the first replacement, problems, such as inexplicable motor overload blowouts, started occurring. Those led to the second replacements, which solved nothing. And the motors run hot.

There's been some conjecture that the cinder block housing is insufficient, resulting in condensation in the windings. However, you've noted the housing isn't what has changed and is probably not the source of the problem. What troubleshooting steps should you take next?

You should strongly suspect motor installation errors. One common problem is the misuse of solderless connectors. These connectors are designed to grab and mechanically connect the wires as you twist the connector on. If you twist the wires together first, the mechanical connection is poor; it's likely to become a high-impedance connection.

The poor connections resulting from this misuse usually exhibit different impedances, which means voltage imbalance on the motor. That would explain the "run hot" part.

  • Disassemble the connections.
  • Conduct insulation resistance testing and AC resistance testing on the branch circuit wiring.
  • Before reconnecting the motor, clean the wires with copper cleaning compound.
  • Check the entire installation for bonding errors. This is load side equipment, so nothing should be "grounded" (see Art. 100 definition).

To determine where to look next, conduct vibration analysis and power quality analysis while the compressor's in the loading phase.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.