Code Quandaries

Stumped by the Code?

All questions and answers are based on the 2005 NEC.

Q. Where in the Code does it say that sharing a neutral is acceptable?

A multiwire branch circuit is a circuit with two or more ungrounded conductors having a voltage between them, with equal voltage between the ungrounded conductors and the neutral conductor.

A. Article 100 defines a multiwire branch as two or more ungrounded circuit conductors with a common grounded (neutral) conductor. There must be a voltage potential between the ungrounded conductors and an equal voltage potential from each ungrounded conductor to the grounded (neutral) conductor (Figure).

Multiwire branch circuits offer the advantage of fewer conductors in a raceway, smaller raceway sizing, and a reduction of material and labor costs. In addition, they can reduce circuit voltage drop by as much as 50%. However, because of the dangers associated with multiwire branch circuits, the NEC contains additional requirements to ensure a safe installation. See 210.4, 300.13(B), and 408.41 for more information.

Q. When are bonding bushings required on metal electrical raceways?

A. Bonding bushings are one of the methods that can fulfill the NEC requirements for bonding of service raceways, 277/480V systems, and in hazardous (classified) locations. Here are some details:

  • When a metal service raceway terminates to an enclosure with a ringed knockout, a listed bonding device (such as a bonding wedge or bonding bushing) must bond one end of the service raceway with a bonding jumper sized in accordance with Table 250.66 [250.92(B)(4) and 250.102(C)]. If ringed knockouts are not encountered, you can use a bonding locknut instead of a bonding wedge or bonding bushing.

  • Metal raceways or cables, containing 277V or 480V circuits, terminating at ringed knockouts must be bonded to the metal enclosure with a bonding jumper sized in accordance with Table 250.122, based on the rating of the circuit overcurrent protection device [250.97, 250.102(D)].

  • Because of the explosive conditions associated with electrical installations in hazardous (classified) locations, electrical continuity of the effective ground-fault current path (metal parts of equipment and raceways) must be ensured by one of the methods specified in 250.92(B)(2) through (4). A bonding bushing is one of the acceptable methods [250.100].

Q. When sizing the feeder conductors on the load side of a 1,200A adjustable trip breaker, can the conductors be sized to the 1,100A adjustable long-time trip setting of the circuit breaker?

A. As a general rule, the ampere rating of an adjustable circuit breaker is equal to its maximum long-time pickup current setting, and that maximum would be used for sizing conductors [240.6(B)]. However, if the adjustable-trip circuit breaker has restricted access to the adjusting means, then the ampacity of the conductors can be sized based on the adjusted long-time pickup current settings [240.6(C].

In sizing conductors, remember Sec. 240.4(C) says that if the circuit's overcurrent protection device exceeds 800A, then the conductor ampacity, after ampacity adjustment and/or correction must have a rating not less than the rating of the overcurrent device.

Example: An 1,100A protection device can be used to protect three sets of 500kcmil conductors per phase, where each conductor has an ampacity of 380A at 75°C, in accordance with Table 310.16.

Q. Can I install the meter and service disconnect directly below a window, if it's supplied by an underground service lateral?

A. The Code does not restrict the area below a window for the installation of service equipment. Interestingly, the Code does not specify a minimum mounting height for the service disconnect except the 2-foot minimum for mobile homes [550.32(F)]. It does, however, specify that the maximum height from the center of the grip of the operating handle of a switch or circuit breaker used for service equipment, in its highest position, must not be more than 6 feet 7 inches above the floor or working platform [240.24(A)].

Note: The Code does not define an acceptable height for the meter, but most electric utilities require it to be mounted near eye level. Therefore, check on local requirements that may apply to the meter height.

Q. What are the NEC requirements for the minimum distance that receptacles and switches must be from the bathtub/shower space?

A. According to 406.8(C), receptacles must not be installed within or directly over a bathtub or shower stall, and switches can be located next to, but not within, a bathtub, hydromassage bathtub, or shower space [404.4, 680.70, 680.72].

Note: Switches must be located no less than 5 feet from pools [680.22(C)], outdoor spas and hot tubs [680.40], and indoor spas or hot tubs [680.43(C)]. Receptacles must be located no less than 5 feet from an indoor spa or hot tub [680.43(A)(1)]. Hydromassage bathtubs are treated like bathtubs [680.72].

Q. Does the Code allow the use of single-pole light switches for single line-to-line lighting, or must I use a 2-pole switch?

A. The Code does not have any requirements for the number of conductors needed to be opened to control a single line-to-line load. However, if you are using a circuit breaker for switching, you must use a 2-pole circuit breaker or two individual single-pole circuit breakers with handle ties identified for the purpose [240.20(B)(2)].






Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues