The Path of Least Resistance

Jul 1, 2001 12:00 PM, By Mike Holt, Mike Holt Enterprises, Inc.

Contrary to popular belief, electricity takes all paths available — in inverse proportion to the impedance of the paths. The magnitude of the current flowing in a path depends on the path's voltage and impedance. The lower the impedance (assuming voltage remains constant), the greater the current. Conversely, the higher the impedance (assuming voltage remains constant), the lower the current.


Imagine two unequally sized resistors in parallel. The current flowing through one resistor depends on the size of that resistor — not the one next to it. Assuming an infinite power supply, you could add 1000 resistors in parallel and the current in that one resistor wouldn't change.

IEEE Std. 80 uses a value of 1000 ohms for the human body for touch voltage calculations. A 25-ohm ground rod in parallel with a 1000-ohm human will not make an installation any safer from electric shock. For example, if you touch a metal pole energized by a 120V line-to-case fault and there's no effective fault current path, the touch voltage will be enough to kill you — even if you bond the metal pole to a ground rod with a measured ground resistance of 25 ohms. The Figure helps illustrate the following:

  1. A ground rod with a resistance of 25 ohms does not provide an effective fault current path. The pole will remain energized with dangerous touch voltage because the fault current will be only 4.8A (I=120V÷25 ohms). This is not enough to trip a 15A breaker.

  2. Electrons take all available paths, and one of those paths is your 1000-ohm body.

  3. OSHA and NFPA 70E say dangerous touch voltage is anything over 30V. Death from electrocution can occur from as little as 50mA in a few seconds. Touch voltage from an energized object is about 75% of the line-to-case voltage. So a 120V line-to-case fault results in a touch voltage of 90V. This can result in 90mA flowing through the human body indefinitely.

For many years, the street lighting and traffic signaling industries used ground rods, without an effective fault current path, to ground metal parts of an electrical system. Electricians thought these installations were safe because “electricity takes the least resistive path, and it bypasses high resistive paths.” Unfortunately, such thinking resulted in several deaths. This thinking still exists. Some equipment installation instructions require a ground rod without an equipment grounding conductor, claiming it's a safe installation. Electricity does take low-resistance paths, including the one of least resistance. But it also takes every other path available to it. You can't suspend Ohm's Law and Kirchhoff's Law by driving 10 ft of copper-clad steel into dirt. To make an installation safe, ensure the touch voltage on metal parts never exceeds 30V for more than a few seconds. You can do this by bonding all metal parts to an effective fault current path in accordance with Art. 250.




Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

Whats Wrong Here?

Mar 11, 2010 12:54 PM

What's Wrong Here?

Feb 18, 2010 5:04 PM

What's Wrong Here?

Feb 4, 2010 5:06 PM

View all What's Wrong Here?

product of the week

CAD Software

March 15, 2010

CAD Software

View all 2010 Products of the Week

Shocking Stats

54
More Industry Statistics

Recent Comments

More...




Professionals provide answers to your questions. Become an expert!


EC&M TV

Arlington CED1 Entrance Hoods

The Scoop Series CED Entrance Plates and Hoods are reversible, non-metallic, single and two-gang versions...

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar!

George Brown College

Online Tech Training – Electronics, PLC, and Robotics programs at George Brown College.

 

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues