Line Reactors and VFDs

Find more articles on: Variable Frequency Drives


Line reactors can protect motors and reduce power line distortion from VFDs.

Do you have problems with your existing variable-frequency drives (VFDs)? If so, 3-phase line reactors may be a very viable solution. A line reactor acts not only as a current-limiting device, but it also filters the waveform and attenuates electrical noise and transients associated with the system. You can install reactors in HVAC equipment, pumping equipment, machine tools, elevators, printing presses, UPS equipment, computer mainframes, robotics equipment, ski lifts, wind generators, electric cars, cranes, trams, and many other types of equipment, to extend the service life of the VFD and motor.


Harmonic attenuation. As the name implies, you'd typically use line reactors on the line side of a VFD, as shown in Fig. 1 at right. Harmonic compensated line reactors are specially designed to handle the waveform's harmonic content. By inserting inductive reactance into the circuit, which is a high impedance to harmonic frequencies, line reactors reduce the amount of harmonics produced by a VFD system. For harmonic reduction purposes, you typically apply 5% impedance line reactors to the input of motor drives 20 hp and higher. This reduces input harmonics to 35% total harmonic current distortion (THID) or less and minimizes the effects of harmonics on motors and other devices powered off the same electrical system.

Drive protection.

In situations where you have drives located very close to the incoming facility power source, such as a substation, they may be susceptible to any incoming spikes and other transients. This is because there may not be enough impedance (in the form of transformers, power feeders, and the like) to help counteract these transient voltage spikes. This situation can damage the front end (diode section) of the drives or cause nuisance overvoltage tripping on the system. Installing a 5% impedance line reactor at the input to each drive helps counteract line spikes, keeping them from tripping or damaging the drives.

On the other hand, if you have drives located far from the facility power source (as often seen in hospitals), they may be affected by line harmonics caused by other harmonic-generating equipment (nonlinear loads). In most applications, harmonic problems are best solved at their source. Look for large nonlinear loads, such as VFDs, and apply a 5% impedance line reactor on the input to those pieces of equipment to minimize the system harmonics.

Motor protection. A reactor that is compensated for high frequencies and protected against fast rising voltage pulses is a very effective dv/dt (rate of change of voltage with respect to time) filter, and you can use it on the load side of the drive (between the drive and motor). Fast changing pulse-width modulation (PWM) voltage pulses in PWM drives can interact with the distributed inductance and capacitance of long motor leads. This, in turn, can result in amplified peak voltages as high as 1,600V at motor terminals. In fact, the longer the cable length, the higher the peak overvoltage at the motor terminals.

This phenomenon, known as long lead effect, can stress and consequently degrade the insulation around the stator windings of motors, resulting in shorter motor life. Some have tried to compensate for the higher frequencies and harmonic currents present in the drive output waveform by oversizing the unprotected motor. A general practice is to use a 5% impedance load reactor on the load side of a VFD when the motor lead length is greater than 100 ft. Typically, you can use two 5% impedance reactors in series (10% impedance) if the motor leads exceed 1,000 ft in length.

Motor noise reduction. To reduce the audible motor noise and telephone interference factor associated with PWM drive switching rates between 1 kHz and 8 kHz, manufacturers developed VFDs with switching frequencies as high as 20 kHz. While the higher frequencies did reduce motor noise, they also aggravated PWM pulse contribution to excessive motor-shaft voltage and current that can discharge across motor bearings. VFDs that use insulated-gate bi-polar transistors (IGBTs) as high-frequency switches are most likely to cause bearing discharge current.

Where a motor, by necessity, is extremely far from its drive, you can install a high-frequency compensated reactor on the load side of the drive, either at the drive end or motor end, to help protect the motor from overvoltage, stress from PWM voltage pulses, overheating and resulting stator insulation degradation, while reducing the motor whine.

VFD protection. The load reactor also acts as a current-limiting device to protect the drive under motor short circuit conditions. Here, the line reactor slows the rate of rise of the short-circuit current and limits the current to an acceptable level.

By slowing the rate of rise of current, the reactor allows time for protection circuits in the drive to react to the short circuit and trip out safely, saving the IGBTs. The reactor also absorbs current surges created by the motor load that might otherwise cause nuisance tripping of the drive. Machine jams, multiple motor switching, and other application changes to the drive load cause motor load surges. Fig. 2 shows reactors on the load side of single and multiple motors.

Looking at the load side reactor from the motor view, the ability of the reactor to filter the waveform produced by the VFD improves the performance of both the motor and the total system.

Summary of possible reactor performance. The installation of load reactors with drives and motors can reduce the high-frequency currents in the motor and protect the motor from long lead effects. Basically, the reactor attempts to recreate a sine wave, thus improving overall system performance, reliability, and efficiency. It may reduce audible motor noise by as much as 3 dB to 5 dB. Tests have shown motor temperatures can drop as much as 20°C (more than double the motor life) when using a harmonic-compensated 5% impedance load reactor.

On the line side, reactors stabilize the current waveform, which reduces harmonic distortion and the burden on upstream electrical equipment. By absorbing line spikes and filling some sags they can prevent overvoltage and undervoltage tripping problems. For example, when the utility switches power factor correction capacitors on the electrical power grid, it creates voltage spikes. The impedance of the reactor in the input circuit helps prevent these voltage spikes and virtually eliminates nuisance tripping of drives due to overvoltage.

A line reactor can also filter out pulsed and notched distortion, which can minimize interference with other electronic equipment like computers, PLCs, telecommunications systems, instrumentation, and other VFDs.

The use of line and load reactors increases the reliability, performance, and efficiency of VFD systems, extends the life of both drives and motors, and reduces the amount of energy consumed by the motor/drive system.

Houdek is VP of marketing and sales with MTE Corp., Menomonee Falls, Wis.


Want to use this article? Click here for options!





Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues