Keeping up with Category 5 cabling requirements in a horizontal run.

Most high-speed cable system failures are caused by excessive bending, twisting, or pulling stress, or by improper termination procedures. For example, excessive force on the cable (due to stress during installation or an improper cable support device), can alter the pair geometry within the cable assembly, causing an increase in return loss, attenuation, or near-end crosstalk.

An installer who recently installed Category 5 cable using bridle rings and tie-wraps as the main means of support came upon a difficult scenario. Despite his care in installation, the cable did not work because the ring and tie-wraps allowed excessive bending and stress at specific points of the cable. After reworking the job using a recommended support device, the cabling system performed according to specs.

Code requirements

The National Electrical Code specifies that in a horizontal cable run from a telephone closet to a work area, only approved cable support methods should be used, such as J-hook fasteners, cable tray, and wireway. All of these provide the broad, continuous support required by high-performance cable to avoid bending stress or failure.

J-hook fasteners typically are the most widely used of the three methods because they offer speed and economy in installation and are easy to reconfigure, if necessary. These J-hook hangers are available in two sizes: The large J-hook can accommodate up to 75 four-pair UTP cables; while the small J-hook can accommodate up to 50 four-pair UTP cables. The J-hook can also hold fiberoptic cable or inner duct.

J-hooks recommended for use with Category 5 copper cables have a wide base loop with rounded smooth curves to spread the weight of the cable bundle and reduce the possibility of snag as cabling is pulled. A closure tie prevents cables from slipping. For main cabling routes, "tree" assemblies made of multiple J-hooks can be used.

Installation options

The easiest way to install cable supports is by connecting them with prefabricated clips on ceiling support wires or rods. However, due to recent NEC changes (Sec. 300-11), you may no longer be able to install cable supports on existing ceiling support wires, rods, or acoustical tees. So, you may have to install additional dedicated drop rods or drop wires. (Check with the Authority Having Jurisdiction [AHJ] or local inspector.) You can hang cable supports from existing beams and trusses, using prefabricated I-beam clamps, C- or Z-purlin clips, and other fasteners. For example, an I-beam clamp (100-lb load rating) is attached directly to the bottom cord of a web truss or a solid I-beam in the ceiling.

Generally, J-hook fasteners should be placed at 4-ft to 5-ft intervals so the cables are properly supported and lower cables are not stressed and deformed due to the weight of the cable bundle.

While attaching cable supports, the installer should maintain the minimum distances from sources of electromagnetic interference: 6 in. from power circuits of 2 kVA or less, 1 ft from high-voltage (arc discharge) lighting, such as fluorescent and HID lamps, 3 ft from power conductors of 5kV or higher, and 3.5 ft from transformers and motors.


Want to use this article? Click here for options!





Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues