Fundamentals Of Harmonics Testing And Mitigation

Correctly measuring and interpreting voltage and current waveforms are critical when you're trying to determine what's behind any power quality problem.

Since so many types of loads can cause harmonic currents, finding the culprit behind your power quality problem is anything but predictable. Adjustable speed drives, electronic ballasts, data processing equipment, and uninterruptible power systems are just a few of the devices that generate harmonic currents. However, their presence does not necessarily mean the phenomenon of harmonics exists. One of the most difficult things to determine in power quality analysis is whether a site is a prime candidate for harmonic problems. To help you in your troubleshooting efforts, let's look at the proper methods of measuring harmonic voltages and currents as well as review some rules for deciphering the results.

Voltage and current measurements. Troubleshooting a power system for a suspected harmonics problem must include voltage and current measurements made with true RMS (root-means-square) digital meters. By using such a meter, you can accurately determine the voltage and current amplitudes in the presence of non-sinusoidal loads. Most meters used today are average-responding RMS, meaning they measure the amplitude of the waveform and multiply it by 1.414.

Although the readings would be the same on circuits feeding linear loads, the results from average-responding meters can be misleading on those with nonlinear loads. Voltage readings taken from the average-responding meter are greater than those made with a true RMS meter. However, current readings from average-responding ammeters are less than measurements made by true RMS ammeters. Because of this discrepancy, you can see how using the wrong type of meter can affect everything from kVA calculations to conductor sizing.

Other meters provide graphic representation of the harmonics waveform. Spectrum analyzers, oscilloscopes, power disturbance monitors, and harmonic analyzers are just a few. These can display the waveform distortion and calculate the exact level of harmonic distortion at various frequencies. Infrared meters find overheated connections in electrical panelboards or transformer windings, especially along the neutral conductor path.

Voltage and current distortion. To simplify your investigation, it helps to divide harmonic problems into two categories: voltage waveform distortion and current waveform distortion. Voltage distortion concerns electric utilities more than current distortion because it affects electrical delivery to the facility.

IEEE standard 519-1992, Recommended Practice and Requirements for Harmonic Control in Electric Power Systems, states the total harmonic distortion (THD) of the voltage waveform provided by the utility cannot exceed 3% of the ideal sine wave. Make this measurement at the point of common coupling (PCC). This is where the utility and facility wiring meet (usually at the meter box). If the voltage distortion exceeds 3%, the utility should provide some form of mitigation to correct the problem.

Why does voltage and current waveform distortion concern you? Distorted voltage waveforms affect the RMS input voltage for equipment. In some cases, they occur too far downstream from the PCC for the utility to monitor it accurately. It's best to measure the voltage waveform distortion at the effected equipment location. Taking measurements at the suspected source of distortion will also help you find a solution.

High levels of harmonic current can overload the facility's wiring and electrical equipment. The overriding concern for current waveform distortion is THD versus the actual loading of the equipment power source. For example, let's say you determine the current waveform from a personal computer has a harmonic distortion of 75%. Although this appears high, the amplitude of the current is relatively low (maybe 2A).

This may have little impact to the overall harmonic distortion of the voltage sine wave if the power source is lightly loaded. As with voltage waveform distortion, the best location to measure current waveform distortion is at the power source that feeds the equipment location (i.e., isolation transformer or main service entrance). This gives you the best representation of the overall current waveform distortion. Remember: This distortion should not exceed 4% at any point of the facility's electrical distribution.

Although nearly all of the loads used today in the commercial and industrial sector generate harmonics, some believe complications from harmonics make up less than 3% of all power quality problems. What's the lesson here? Harmonics is not necessarily a problem just because of a customer's nonlinear loads.


 

Want to use this article? Click here for options!





Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues