Ask the Experts
Defining Harmonic Terms
Anyone will tell you, if you're going to have any success in dealing with power quality problems — particularly with issues of a harmonic nature — you're going to have to know your definitions. This month, John DeDad, EC&M's editorial director, takes a look at positive, negative, and zero sequence harmonics and explains how they affect different equipment.
Q. In some harmonic mitigation product literature, I've seen the terms “positive sequence,” “negative sequence,” and “zero sequence” used to refer to specific harmonic currents. What do these terms mean and why are they important?
DeDad's answer: Positive sequence harmonic currents are the 1st, 7th, 13th, 19th, etc. harmonics. They consist of three phasors, each equal in magnitude but separated from each other by a 120° phase displacement. These harmonic currents have the same phase sequence as phasors that represent normal 60-Hz current.
Table 1. Once you learn the pattern, you’ll always be able to identify which harmonic current goes with which sequences. Note that the triplen harmonics are those with a zero sequence.
Negative sequence harmonic currents are the 5th, 11th, 17th, etc. harmonics. Like positive sequence harmonic currents, they consist of three phasors, each equal in magnitude but separated from each other by a 120° phase displacement. However, these phasors have a phase sequence opposite to phasors that represent normal 60-Hz current.
Zero sequence harmonic currents are the 3rd, 9th, 15th, etc. harmonics. They consist of phasors equal in magnitude but with zero displacement from each other. Because these phasors are concurrent in direction, they produce an amplitude three times greater than any one phasor when they combine on the neutral of an electrical system. You'll also see these harmonics referred to as triplen harmonics. PCs, older versions of electronic ballasts, and phase-to-neutral nonlinear loads typically generate these harmonic currents (Table 1 at left).
Specific harmonics are associated with various types of equipment. For example, phase-to-phase nonlinear loads, such as equipment with six-pulse rectifiers, generate high levels of 5th and 7th harmonics, with lower levels of the 11th and 13th harmonics. Equipment with 12-pulse rectifiers generate the same harmonic currents but substantially lower levels of the 5th and 7th (Table 2 here).
Got a PQ problem? E-mail your question to jdedad@primediabusiness.com
Want to use this article? Click here for options!
© 2012 Penton Business Media, Inc.
Latest Articles
EV charger tester
May 25, 2012 8:26 AM
CFL/LED dimmer
May 24, 2012 8:48 AM
Load bank
May 23, 2012 9:33 AM
Trending Articles
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.