Code Violations Illustrated


As usual, never consider the following commentary associated with these photos as a formal interpretation of the National Electrical Code (NEC). Without criticizing anyone or any product, the following scenarios present us with serious electrical safety questions.



Call of the Wild

Electrical/mechanical engineer Michael L. Stoianoff, P.E., found this 200A panelboard serving a residential property in rural Alaska. Although it was too faded to read, an approved electrical inspection sticker was affixed to the panelboard. However, there were no circuit directory markings anywhere. In the case of a panelboard, the Code requires all circuits and circuit modifications to be legibly marked by means of a circuit directory located on the panelboard's face, or inside its door. This installation violates 110.22 and 408.4 of the 2002 NEC.

The smaller photo shows receptacles installed directly below for an unknown purpose. Interestingly, the circuit breakers were mounted behind the receptacle boxes. Apparently the conductors were run in a channel cut into the building's wood exterior. There were nine circuit breakers in all, two of which were rated 100A and one 50A. This installation violates Art. 230 and 408, Part III of the 2002 NEC.

Stoianoff also discovered that although the nonmetallic sheathed cable equipment grounding conductors in the branch circuits were pulled into every outlet box, none of them was properly connected or terminated to the equipment grounding terminal on the devices. They were, however, connected to the equipment grounding terminal bus in each panelboard. This wiring arrangement wreaked havoc on the owner's computer. This installation violates 250.148 and 408.20 of the 2002 NEC.




Not Approved for Wet Conditions

These soda machines are located in a wet area on the platform of a train station in North Quincy, Mass. Sec. 406.8(B), which covers 15A and 20A outdoor receptacles installed in a wet location, requires these devices to have a weatherproof enclosure, whether or not the attachment plug cap is inserted.

Any receptacle installed in a wet location and powering an unsupervised piece of equipment, such as a sprinkler system controller, landscape lighting, or holiday lights, must have an enclosure that is weatherproof whether the attachment plug cap is inserted or removed. Also, a receptacle installed in a wet location and powering an unsupervised piece of equipment, such as portable tools, must have an enclosure that is weatherproof when the attachment plug is removed.

Now you can send Code Violations Illustrated stories and photos directly to Joe Tedesco at:
Joe Tedesco
350 North Street
Boston, MA 02113
or e-mail:
codeviolations@netscape.net

If you mail pictures, please include the story, location, and some information about yourself — and please do not write on the front or back of your photo. Please send all digital images in JPEG format. You can send photos while visiting Joe's Web site at: www.joetedesco.com


Want to use this article? Click here for options!





Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues