Code Calculations

You must size pull boxes and junction boxes, as well as conduit bodies (enclosures), so you don’t damage the conductor insulation. For conductors No. 4 and larger, size pull boxes, junction boxes, and conduit bodies according to the National Electrical Code (NEC) Sec. 370-28.

Straight pull calculation [Sec. 370-28(a)(1)]. A straight pull calculation applies when conductors enter one side of an enclosure and leave through the opposite wall of the enclosure. The minimum distance between these walls must not be less than eight times the trade size of the largest raceway.

Angle pull calculation [Sec. 370-28(a)(2)]. An angle pull calculation applies whenever conductors enter one wall of an enclosure and leave through the adjacent wall (not opposite the wall). The minimum distance (from the wall where the raceway enters to the opposite wall of the enclosure) must not be less than six times the trade diameter of the largest raceway, plus the sum of the diameters of the remaining raceways on the same wall and row. When more than one row exists, you must calculate each row separately. The row with the largest calculation is the minimum angle pull dimension.

U pull calculations [Sec. 370-28(a)(2)]. A U pull calculation applies when the conductors enter and leave an enclosure from the same wall. This distance must not be less than six times the trade diameter of the largest raceway, plus the sum of the diameters of the remaining raceways on the same wall.

Distance between raceways calculation [Sec. 370-28(a)(2)]. After sizing the enclosure, be sure to install raceways so the distance between raceways enclosing the same conductors are not any closer than six times the trade diameter of the larger raceway. Measure this distance from the nearest edge of one raceway to the nearest edge of the other.

Depth of enclosure [Sec. 370-28(a)(2), exception]. When conductors enter an enclosure opposite a removable cover such as the back of a pull box or conduit body the distance from the wall where the raceways enter to the removable cover must not be less than the distances listed in Table 373-6(a); one wire per terminal.

Example No. 1—sizing a pull box. A pull box has one 4-in. raceway on the left side, one 4-in. raceway on the bottom, and one 3-in. raceway on the top and right side.

Q. What is the horizontal dimension of the box?

(a) 28 in.
(b) 21 in.
(c) 24 in.
(d) none of these

A. Sec. 370-28(a)(2) requires you to size the box based on the larger raceway.

Left wall to right wall (angle pull) = 6 x 4 in. = 24 in. Therefore, the answer is (c) 24 in.

Q. What is the vertical dimension of the box?

(a) 18 in.
(b) 21 in.
(c) 24 in.
(d) 14 in.

A. Again, the answer is (c) 24 in. based on the same calculation and reference above.

Determine the minimum distance between the two 4-in. raceways (containing the same conductors) in the same manner as above (i.e. 6 x 4 in. = 24 in.).

Example No. 2—sizing a junction box. A junction box contains two 3-in. raceways on the left side and one 3-in. raceway on the right side. You must pull the conductors from one of the 3-in. raceways on the left wall through the 3-in. raceway on the right wall. You then pull the conductors from the other 3-in. raceway through a 3-in. raceway at the bottom of the pull box.

Q. What is the horizontal dimension “A” of the box?

(a) 18 in.
(b) 21 in.
(c) 24 in.
(d) none of these

A. Sec. 370-28(a)(1) requires you to size the box for the straight pull based on the following calculation:

Left wall to right wall (straight pull) = 8 x 3 in. = 24 in.

Right wall to left wall (straight pull) = 8 x 3 in. = 24 in.

Sec. 370-28(a)(2) requires you to size the box for the angle pull based on the following calculation:

Left wall to right wall (angle pull) = (6 x 3 in.)+ 3 in. = 21 in.

Right to left wall (angle pull) = no calculation.

The largest answer you calculate governs the horizontal dimension of the box. Therefore, the answer is (c) 24 in.

Q. What is the vertical dimension “B” of the box?

(a) 18 in.
(b) 21 in.
(c) 24 in.
(d) none of these

A. In this case, you only need to perform one calculation. Bottom wall to top wall (angle pull) = 6 x 3 in. = 18 in. Therefore, the vertical dimension of the box is (a) 18 in.

Q. What is the minimum distance “C” between the two 3 in. raceways that contain the same conductors?

(a) 18 in.
(b) 21 in.
(c) 24 in.
(d) none of these

A. Determine the minimum distance between the two 3-in. raceways (containing the same conductors) in the same manner as above (i.e. 6x 3 in. = 18 in.).

Q. If the enclosure has two 2-in. conduits that enter the back with No. 4/0 conductors, what is the minimum depth of the enclosure?

(a) 4 in.
(b) 6 in.
(c) 8 in.
(d) 10 in.

A. You determine the depth of the enclosure as per Table 373-6(a). Assuming our installation uses one wire per terminal, the answer is (a) 4 in.






Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues