Multiple Grounding Points Can Cause DCS Failures

If your facility has a modern distributed control system with a reading "offset" problem, the grounding system could be the cause.and the remedy.

One of the really great things about modern distributed control systems (DCSs) is once they're set up and operational, readings are steady and repeatable. In fact, they're so reliable that common programming relies on the DCS to serve as the watchdog over many processes with full authority to "trip" when values stray outside of predefined "windows" or maximum and minimum values. This is a valuable feature until the DCS trips the system due to a faulty value or, even worse, it trips at random times that are seemingly unrelated.

Recent history has shown multiple grounds can change the values the DCS computer reads, thus causing erroneous output values, that fall outside of operational limits. These multiple grounds can come from the most unexpected points.

Every DCS installation has a safety ground that's essentially the same as the static grounding system. The system also has a reference ground you can temporarily disconnect from the safety ground for troubleshooting purposes. However, you'll typically only find both connected together at the DCS computer bus. You won't find cable shields and shield-drain wires connected to ground at field junction boxes, because doing this causes a parallel path where circulating currents of varying magnitudes could flow. This situation also compromises cable shielding. Accidental grounds anywhere away from the main DCS reference grounding bus can cause circulating currents. These varying loop values can show up as valid data in the DCS computer as it crunches numbers, which leads to inaccurate results.

To produce shielded cables, manufacturers shield the twisted pair with a foil layer that's in contact with an uninsulated "drain" wire. They cover these three conductors with a jacket (sometimes with armor and an additional jacket). When terminating a cable in the marshalling cabinet, the jacket is frequently stripped at the cable gland where the cable passes through the sheet metal of the grounded marshalling cabinet enclosure. This leads to a myriad of twisted wire pairs and drain wires traveling vertically down into the marshalling cabinet section within the plastic wireways until each "peals off" to land on its appointed terminal block.

This type of configuration places the drain wires in intimate contact with one another at multiple locations. Normally, this arrangement wouldn't be a problem except that metal screws (whose screw heads are on the cable side of the plastic wireway) typically hold the plastic wireway into the marshalling cabinet. At this location, one drain wire touching a screw head electrically connected to the grounded marshalling cabinet leads to an offset voltage or circulating currents.

The only positive "fix" is to remove each drain wire from its terminal block and slide insulating spaghetti up to the point where the jacket ends in the gland. This simple solution insulates the drain wire from the gland, from other drain wires, and from the wireway mounting screws.


Want to use this article? Click here for options!





Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues