Don’t Leave Arc Flash Protection to Chance — Part 2

Labeling standards based on arc flash risk

The second in a three-part series on the importance of arc flash labeling of electrical equipment, this set of articles provides practical examples to shed light on some of the common misconceptions surrounding arc flash protection.

In Part 1, which ran in the September 2011 issue, we considered the low-level task of taking measurements within a non-fused safety switch that serves as a local motor disconnect. In this piece, we learned that the level of arc flash risk for this task cannot be taken lightly, because it depends significantly on the amperage and class of the upstream fuses in the motor starter compartment and the length of the branch circuit conductors running from the fuses to the safety switch.

In this installment, we focus on the example system outlined in Fig. 1 (click here to see Fig. 1). Work is to be done at the next upstream level device of the electrical system (i.e., in the combination motor starter bucket of a motor control center or MCC serving a low-voltage induction motor). Unfortunately, the door of the bucket is missing an NFPA 70E-compliant arc flash warning label. Therefore, the worker cannot be sure of the level of arc flash risk at this specific location. So how should one proceed when no warning label is present?

As shown in Fig. 1, the upstream protective device that should respond to an arcing fault in the motor starter bucket is a low-voltage power circuit breaker equipped with a solid-state trip unit. The effect of the long-time (LT), short-time (ST), and instantaneous (I) settings of the trip unit are shown on the time-current plot in Fig. 2 (click here to see Fig. 2). The degree of separation of the fuse and circuit breaker time-current characteristics in the “I” region is due to the “I” pick-up setting. This setting guarantees selective coordination of these protective devices below 0.1 sec for a fault on the load side of the fuses. It’s important to note that selective coordination can still be achieved at a lower “I” pick-up setting. For a discussion on this topic, see the article “Protective Device Coordination Study — Part 2 of 3,” which appeared in the March 2011 issue of EC&M, available online at http://ecmweb.com/design_engineering/protective-device-coordiation-study-part-2-20110301/.

Calculations were performed per IEEE 1584 to determine the incident energy level in Calories per square centimeter and corresponding Hazard/Risk Category (HRC) for variation in feeder length. The results of these calculations are summarized in the Table. As expected, the bolted 3-phase, short circuit current and corresponding arc current at the starter bucket decrease with increasing feeder length. IEEE 1584 recommends using the worst-case results of arc time and incident energy for 100% and 85% of the calculated arc current. These results are summarized in the Table (click here to see Table).

What can you take away from the results shown in the Table? First, the effect of feeder length on incident energy level is not straightforward. As you can see, this value encompasses a wide range of values and covers three different HRCs. Second, the “I” pick-up setting significantly affects the arc time when calculating incident energy, besides its effect on the coordination between the fuses and circuit breaker. Note in the Table that the arc time is either 0.01 sec or 0.19 sec, depending on whether the arc current is above or below the “I” pick-up setting, respectively. Thus, a key take away from this example is that you should not change trip unit settings on the fly without careful consideration of the consequences on protection and life safety requirements.       

Frank Mercede, P.E., is vice-president and Joseph Mercede is president of Mercedes Electric Co., Inc., based in Lester, Pa. They can be reached at: fmercede@mercedeelectric.com and jmercede@mercedeelectric.com.


Want to use this article? Click here for options!





Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

LED replacement lamp

May 22, 2012 8:12 AM

LED replacement lamp

The Array LED BR30 replacement lamp features an enhanced dimming circuit and the company’s second-generation Selective Heat Sink Technology...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Date: Thursday, May 24, 2012
Time: 2:30pm ET


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register Today!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues