OK, it won't be easy, but these five steps will help your next transformer installation run more smoothly.
Discuss this Article 3
your web site is technically very very rich, pls. keep enhancing the website.
How about this situation. I have a 600A 277/480V service. The primary GEC is a 2/0 ground ring encircling the building w/4 rods spaced at 6.5'. Every other steel column of the building has a thermoweld tap from the ground ring. There is a secondary 2/0 GEC to the 2" water main.
Adjacent to the main panel is a 45 KVA transformer. It is fed from the main panel to service the 120/208V load center. In order to bond the X0 of this transformer now;
The engineer asked for a seperate #2 GEC to be terminated on one of the ground rods from the X0, not practical or possible now.
The water main is not in the electric room, however there is a 5" square column next to the transformer and steel bar joists 20' up. Which would be a better choice for #4 GEC from the SDS X0?
A) Tap (irreversable) the 2/0 bare from the counterpoise system (ground ring) inside the main panel
B) Weld to the 5" square column next to the transformer (not tapped from the ring)
C) Send the #4 up the wall in PVC terminate with crimp lug and bolt to the bar joist.
D) The water main in the room next door (20') or tap its 2/0 inside the main panel.
Tapping the 2/0 in the main panel is the least expensive method but is it the best and is the existing 2/0 GEC large enough to add the #4 to it?
I have a problem with a 112.5 KVA XFo, the breaker on the primary keeps on tripping and when I disconnect the secondary leads from the XFo it's OK. When I check my secondary wire with my meter on ohms to find a short , it's
Isame OK . Is there something else that could be causing the breaker to trip? Thanks





