The answer to JK’s question on “failing generator batteries” in June 1997 needs additional information. First, you need to find out why the engine-driven charging system is not working. Usually, there is a voltage regulator to hold constant voltage, so the charging current will taper off as the battery comes up to full charge—about 27½V, depending on the age of the battery. Second, and probably more