Test Your Motor Control IQ

Feb. 1, 1998
What should voltage readings be at various points of a control schematic?Shown here (illustration is in original, printed article) is a wiring schematic of an across-the-line starter with 480-120V control transformer. Based on each of the operating conditions shown below, fill in each table with what you think the voltage readings should be between the points indicated.Condition 1: 480V power ON;

What should voltage readings be at various points of a control schematic?

Shown here (illustration is in original, printed article) is a wiring schematic of an across-the-line starter with 480-120V control transformer. Based on each of the operating conditions shown below, fill in each table with what you think the voltage readings should be between the points indicated.

Condition 1: 480V power ON; Disconnect 1 OPEN; M coil and motor OFF; OL1 contact CLOSED.

Condition 2: 480V power ON; Disconnect 1 CLOSED; M coil and motor OFF; OL1 contact CLOSED.

Condition 3: 480V power ON; Disconnect 1 CLOSED; M coil and motor ON; OL1 contact CLOSED.

Condition 4: 480V power ON; Disconnect 1 CLOSED; M coil and motor OFF; OL1 contact OPEN.

Condition 5: 480V power ON; Disconnect 1 CLOSED; Fuse 1 OPEN; M coil/motor OFF; OL1 contact CLOSED.

Condition 6: 480V power ON; Disconnect 1 CLOSED; Fuse 2 OPEN; M coil/motor OFF; OL1 contact CLOSED.

Answers (in boldface): Condition 1: L1-L3: 480V; T1-T3: 0V; H1-H4: 0V; X2-X1: 0V; X2-A: 0V; X2-B: 0V; X2-C: 0V; X2-D: 0V; X2-E: 0V

Condition 2: L1-L3: 480V; T1-T3: 0V; H1-H4: 480V; X2-X1: 120V; X2-A: 0V; X2-B: 0V; X2-C: 120V; X2-D: 120V; X2-E: 120V

Condition 3: L1-L3: 480V; T1-T3: 480V; H1-H4: 480V; X2-X1: 120V; X2-A: 0V; X2-B: 0V; X2-C: 0V; X2-D: 120V; X2-E: 120V

Condition 4: L1-L3: 480V; T1-T3: 0V; H1-H4: 480V; X2-X1: 120V; X2-A: 0V; X2-B: 0V; X2-C: 0V; X2-D: 0V; X2-E: 120V

Condition 5: L1-L3: 480V; T1-T3: 0V; H1-H4: 0V; X2-X1: 0V; X2-A: 0V; X2-B: 0V; X2-C: 0V; X2-D: 0V; X2-E: 0V

Condition 6: L1-L3: 480V; T1-T3: 0V; H1-H4: 480V; X2-X1: 120V; X2-A: 0V; X2-B: 0V; X2-C: 120V; X2-D: 120V; X2-E: 120V

Contact author at Starrats Technical Services, P.O. Box 436, Riverside, IL 60546; phone 708-484-2477; fax 708-484-2487; and e-mail [email protected].

About the Author

Larry Baran

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...

Champion Strut Catalog

Champion Fiberglass is the most advanced manufacturing facility of fiberglass conduit, fiberglass bridge drain and fiberglass strut systems in the world. Its well-trained and ...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...