The Basics of Bending Conduit — Part 1

June 1, 1999
From measuring to marking to cutting, conduit bending is truly one of the fundamental tasks for an electrician.

Conduit bending is truly one of the fundamental tasks of the electrical construction industry. Whether EMT, galvanized rigid steel conduit, or intermediate conduit, you will need to bend it. Bends will be required as part of your installation. Of course, factory-made elbows are available for feeder sizes (11/4-in. and higher). However, for branch circuit sizes, the trusty hickey is the tool of the day. Let's look at the following step-by-step approach.

Step 1: Remove cutting burrs from the cut conduit end. Before you begin your bend, use a conduit reamer to remove any cutting burrs left after you've made your cut. Some electricians use a knife to swipe the edge of the cut. Don't use a screwdriver; it's not meant for this task and really doesn't work as well.

Step 2: Mark the distance at which the conduit must change direction. Determine where you want the conduit to start. This is usually where the conduit secures inside a fitting. Then, determine where you need the conduit to change directions. For example, if you need a horizontal conduit to run vertically 5 ft from its starting point, then you need the conduit to change directions at 5 ft. Thus, make a mark on the conduit 5 ft from its start point.

Step 3: Mark the middle of the bend. If you need a 90 degree bend 5 ft from the conduit's starting point, then the middle of your bend is going to be somewhat less than the 5-ft distance. Many hand benders have the difference number you need noted right on them. If there is no number, remember this difference equals the radius of your bender. Most benders will have a mark that says "90." Simply measure from that mark to the mark "0." Then subtract that distance from the "change of direction" distance. This is the middle of your bend. Write this number, calling it "bend." Make the measurement near the bottom of the bending shoe, as close to the centerline of the conduit as possible. Mark the conduit to show the middle of the bend.

Step 4. Verify marks will make correct bend. Hold the conduit up to where you intend to install it. Do the "change of direction" and "middle of the bend" marks line up with the result you want? If not, measure again. Remember the motto: "Measure twice, bend once."

Step 5. Make a second verification. Lay the conduit on the floor with the "start" end against the wall. Measure from that end of the conduit until you reach a distance equal to the "bend" number you calculated earlier. Does this line up with the earlier mark you made? If so, continue with the next step.

Step 6: At the middle of the bend, mark a line on the floor. Place the "start" end of the conduit against a wall. Slip the hickey over the other end and line it up with the "bend" mark. If the hickey has a mark that reads "0," line up that mark with the "bend" mark. Pull up on your bender handle until the conduit is vertical. If your bend isn't perfect, you can adjust it by moving the hickey a little to one side of the bend and pulling slightly.

In Part Two, we'll look at how to make an end bend and an offset.

About the Author

Mark Lamendola

Mark is an expert in maintenance management, having racked up an impressive track record during his time working in the field. He also has extensive knowledge of, and practical expertise with, the National Electrical Code (NEC). Through his consulting business, he provides articles and training materials on electrical topics, specializing in making difficult subjects easy to understand and focusing on the practical aspects of electrical work.

Prior to starting his own business, Mark served as the Technical Editor on EC&M for six years, worked three years in nuclear maintenance, six years as a contract project engineer/project manager, three years as a systems engineer, and three years in plant maintenance management.

Mark earned an AAS degree from Rock Valley College, a BSEET from Columbia Pacific University, and an MBA from Lake Erie College. He’s also completed several related certifications over the years and even was formerly licensed as a Master Electrician. He is a Senior Member of the IEEE and past Chairman of the Kansas City Chapters of both the IEEE and the IEEE Computer Society. Mark also served as the program director for, a board member of, and webmaster of, the Midwest Chapter of the 7x24 Exchange. He has also held memberships with the following organizations: NETA, NFPA, International Association of Webmasters, and Institute of Certified Professional Managers.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Don't Let Burn-Through Threaten Another Data Center or Utility Project

Get the No Burn-Through Elbow eGuide to learn many reasons why Champion Fiberglass elbows will enhance your data center and utility projects today.

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.