Surge-Protective Device Conductor Length

April 9, 2014
The requirements for surge-protective devices (SPDs), 1kV or less, are outlined in Art. 285 of the 2011 NEC.

The conductors used to connect the surge-protective device to ground shall not be any longer than _____ and shall avoid unnecessary bends.

a) 6 inches
b) 12 inches
c) 18 inches
d) necessary

See answer and applicable Code reference

The correct answer is: d) necessary

The requirements for surge-protective devices (SPDs), 1kV or less, are outlined in Art. 285 of the 2011 NEC. As noted in Sec. 285.12, "The conductors used to connect the SPD (surge arrester or TVSS) to the line or bus and to ground shall not be any longer than necessary and shall avoid unnecessary bends."

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...

A Powerful Duo: Fiberglass conduit and solar applications

Learn how strong, durable fiberglass conduit excelled in an environment with dense cable and helped make a complex burial much simpler for the contractor to help this customer...

Champion Fiberglass® Conduit Protects Cabling For New York's First Offshore Wind Farm

Learn how fiberglass conduit supported a heavy cable load and a buried installation to help this project reach a successful outcome.