Support Requirements for RMC

June 17, 2014
Securing and supporting requirements for RMC are outlined in Sec. 344.30 of the 2011 NEC.

Horizontal runs of RMC supported by openings through _____ at intervals not exceeding 10 ft and securely fastened within 3 ft of termination points shall be permitted.

a) walls
b) trusses
c) rafters
d) framing members

See answer and applicable Code reference

The correct answer is: d) framing members

Securing and supporting requirements for RMC are outlined in Sec. 344.30 of the 2011 NEC. The rule states, "RMC shall be installed as a complete system in accordance with 300.18 and shall be securely fastened in place and supported in accordance with 344.30(A) and (B)." As per 344.30(B)(4), "Horizontal runs of RMC supported by openings through framing members at intervals not exceeding 10 ft and securely fastened within 3 ft of termination points shall be permitted."

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Don't Let Burn-Through Threaten Another Data Center or Utility Project

Get the No Burn-Through Elbow eGuide to learn many reasons why Champion Fiberglass elbows will enhance your data center and utility projects today.

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.