Design Guidelines for Dry-Type Transformers

July 17, 2014
Section 450.21 of the 2011 NEC notes the specific provisions applicable to dry-type transformers installed indoors.

Indoor transformers of greater than _____ rating shall be installed in a transformer room of fire-resistant construction.

a) 75kVA
b) 87.5kVA
c) 112.5kVA
d) 250kVA

See answer and applicable Code reference

The correct answer is: c) 112.5kVA

Article 450 covers the installation of all types of transformers. Section 450.21 notes the specific provisions applicable to dry-type transformers installed indoors. As per 450.21(B), "Individual dry-type transformers of more than 112.5kVA rating shall be installed in a transformer room of fire-resistant construction. Unless specified otherwise in this article, the term fire resistant means a construction having a minimum fire rating of 1 hour."

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.

8 Types of Electrical Conduit and Their Uses

Electrical conduit is a tube or raceway used to house and protect electrical wires within a building or structure. From data centers to underground subways to ports and bridges...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

Champion Strut Catalog

Champion Fiberglass is the most advanced manufacturing facility of fiberglass conduit, fiberglass bridge drain and fiberglass strut systems in the world. Its well-trained and ...