Section 700-12(e) requires unit equipment to be permanently fixed in place (i.e., not portable) and all wiring to each unit to be installed in accordance with the requirements of any of the wiring methods in Chapter 3. A flexible cord and plug connection is permitted, provided that the cord does not exceed 3 ft (914 mm) in length. The branch circuit feeding the unit equipment is required to be the

Section 700-12(e) requires unit equipment to be permanently fixed in place (i.e., not portable) and all wiring to each unit to be installed in accordance with the requirements of any of the wiring methods in Chapter 3. A flexible cord and plug connection is permitted, provided that the cord does not exceed 3 ft (914 mm) in length.

The branch circuit feeding the unit equipment is required to be the same branch circuit as that serving the normal lighting in the area, and connected ahead of any local switches. The branch circuit that feeds unit equipment must be clearly identified at the distribution panel.

Emergency illumination fixtures that obtain power from the unit equipment and are not part of the unit equipment must be wired to the unit equipment as required by Section 700-9 and by one of the wiring methods of Chapter 3.

About the Author

Joseph A. Tedesco

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.