NEC in the Facility

April 10, 2012
The concept of "working space" is commonly misunderstood

The concept of "working space" is commonly misunderstood, and consequently adequate working space is commonly not provided. OSHA provides tables with specific numbers, but it gets its numbers from the NEC. You will find this information in Table 110.26(A)(1) and in the various written requirements of 110.26(A) through 110.26(E).

If you look at Table 110.26(A)(1), it basically says you need a minimum of 3 ft of distance between exposed live parts on one side of the working space and grounded live parts on the other. It also says you need a minimum of 3 ft of distance between exposed live parts on both sides the working space, except when the voltage is greater than 150V. Then it's a minimum of 4 ft.

Amazingly, many facility planners extract from this that it would be nice to have pieces of electrical equipment about 3 ft apart, but not an inch more.

Yet the 3 ft minimum is often grossly inadequate. For example, do you really want a tech's backside only inches away from a 100kVA dry-type transformer vent? If the transformer is 3 ft from a panel, that's the situation you have when someone opens that panel for maintenance. It's unsafe.

Section 110.26 requires adequate safe working space, which may include enough space for test carts, maintenance equipment, lights, and multiple people.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.