Ecmweb 8564 Hydroelectric1200

Grant County PUD Fined for Safety Violations Connected to Electrical Explosion

April 19, 2016
Grant County Public Utility District #2 has been fined $35,000 for five serious safety violations following an explosion at its Priest Rapids Dam in Beverly, Wash.

Grant County Public Utility District #2 has been fined $35,000 for five serious safety violations following an explosion at its Priest Rapids Dam in Beverly, Wash. Six workers were hospitalized with very serious electrical burns from the incident last October.

Under supervision, the workers were troubleshooting a mechanical problem with a generator. The workers did not know that a circuit had been re-energized when they closed a breaker, which caused the high-voltage electrical arc flash explosion.

An investigation by the Department of Labor & Industries (L&I) concluded that the arc flash could have been prevented if the employer had ensured the use of safety locks and safeguards to prevent the breaker from being closed when other parts of the circuit were energized.

L&I cited the utility district for five serious violations, each with the maximum penalty of $7,000. The investigation found that:

  • The employer did not ensure the use of lock-out/tag-out safety devices to prevent inadvertently closing a breaker that could cause an arc flash.
  • Employees were not briefed on the circuit conditions that affected them and exposed them to risk of arc flash burns and electrocution.
  • Employees were not aware that the lock-out/tag-out devices had been removed from the circuit.
  • One worker was not wearing fire-resistant clothing while working on the hydro-electric equipment.
  • The employer did not provide any records to show it was in compliance with the state regulation on protecting workers from injury due to hazardous energy.

The utility district has 15 days to appeal the citation. Penalty money paid as a result of a citation is placed in the workers’ compensation supplemental pension fund, helping workers and families of those who have died on the job.

Voice your opinion!

To join the conversation, and become an exclusive member of EC&M, create an account today!

Sponsored Recommendations

Electrical Conduit Comparison Chart

CHAMPION FIBERGLASS electrical conduit is a lightweight, durable option that provides lasting savings when compared to other materials. Compare electrical conduit types including...

Fiberglass Electrical Conduit Chemical Resistance Chart

This information is provided solely as a guide since it is impossible to anticipate all individual site conditions. For specific applications which are not covered in this guide...

Considerations for Direct Burial Conduit

Installation type plays a key role in the type of conduit selected for electrical systems in industrial construction projects. Above ground, below ground, direct buried, encased...

How to Calculate Labor Costs

Most important to accurately estimating labor costs is knowing the approximate hours required for project completion. Learn how to calculate electrical labor cost.